Figure 4-38. pre-alarms configuration -41 – Winco DGC-2020 User Manual

Page 111

background image

Figure 4-38. Pre-Alarms Configuration

A

High Fuel Level: Enable or Disable, threshold is adjustable from 0 to 150% in 1 % increments.

B

Low Battery Voltage: Enable or Disable, threshold is adjustable from 6 to 12 Vdc (12 Vdc battery) or 12

to 24 Vdc (24 Vdc battery) in 0.1 Vdc increments. Activation delay is adjustable from 1 to 10 s in 1 s
increments.

C

Weak Battery Voltage: Enable or Disable, threshold is adjustable from 4 to 8 Vdc (12 Vdc battery) or 8

to 16 Vdc (24 Vdc battery) in 0.1 Vdc increments. Activation time delay is adjustable from 1 to 10 s in 1 s
increments.

D

Battery Overvoltage: Enable or Disable, threshold is adjustable from 12 to 32 Vdc in 0.1 increments.

E

Maintenance Interval: Enable or Disable, threshold is adjustable from 0 to 5,000 h in 1 h increments.