Output – KEYENCE SL-V Series User Manual

Page 75

background image

2-14

I/O Monitoring Function

2-51

Fu
nct
ion
s and

Feat

ures

2

SL-V-M-NO2-E

Output

The table below indicated the state of the outputs. The indicator (on the transmitter) changes each time
the wait input (violet wire on the transmitter) turns ON. Output operation of the SL-V can be verified via
these indicators on the transmitter or monitoring the actual change of state on the outputs.

Pulse output through state information output 2

After the wait input turns ON eight times while I/O monitoring function is activated, the checking pulse is

output through the state information output 2. (If the connector cable used is for the NPN output, bar LED
No. 1 on the receiver begins to blink. If the connector cable used is for the PNP output, bar LED No. 2
begins to blink.)

The checking pulses can be output through state information output 2.
The number of checking pulses that can be output is as follows.

See "State Information Output" (page 2-18)
See "Muting function" (page 2-29)

See "Override function" (page 2-45)

Indicators (on transmitter)

Description

When connected to a PNP

input device

When connected to an

NPN input device

Interlock-reset-ready output

Red light

: ON

Light OFF

: OFF

Red light

: OFF

Light OFF

: ON

Alert output

Clear/Blocked Output

AUX

Always light in red

State information output 1

Orange light

: ON

Light OFF

: OFF

Orange light

: OFF

Light OFF

: ON

State information output 2

Always light in red

Muting lamp output

Yellow light

: ON

Light OFF

: OFF

Yellow light

: OFF

Light OFF

: ON

5

5

4

4

3

3

2

2

1

1

WAIT

WAIT

FUNCTION

FUNCTION

OSSD

OSSD

INTER
LOCK

INTER
LOCK

Number of

pulses

Meaning

Pulse output condition

1

Normal operation

• The I/O monitoring function is activated and the wait input turns ON eight times.
• After 2 or 3 pulses described below are output, more than one input that meets the

condition for outputting the pulses is deactivated.

2

Muted condition

Muting input 2 turns ON 0.3 seconds or more after muting input 1 turns ON.

3

Override condition

Either muting input 1, muting input 2, or both turn ON, and the reset input turns ON 0.3
seconds or more after the override input turns ON.

4

Muting lamp error

The SL-V detects a muting lamp error after (2) or (3) described above are output. The
muting lamp turns ON if the muting lamp is in normal operation.

Cable

Self-diagnosis

Series Connection

Interlock

AUX

EDM

Wait

State Information

Alert

Clear/Blocked

Suspension

Fixed

Reduced

Monitoring