2-4

Interlock Function

2-10

Fu
nct
ion
s and

Feat

ures

2

SL-V-M-NO2-E

This section explains the settings other than the combination of automatic start and automatic reset mode.

Configuration

Wiring method (Pink wire on the transmitter)

SL-V can be set as the combination of manual start and manual reset mode through the wiring in the
following manner. If this function is set through the SL-VH1S, it cannot be set through the wiring.

Software method (SL-VH1S)

Refer to the "SL-VH1S User’s Manual".

Wiring

• When using a switch for reset input, use a switch rated at 24 V DC, 2 to 3 mA.

• If the power is turned on with an open circuit on the pink wire (interlock mode selection input), the SL-V

enters the I/O monitoring state.

See "I/O Monitoring Function" (page 2-50).

• If the power is turned on while the yellow wire (reset input) is turned on and the type of cable is incor-

rect, the SL-V goes to the lockout condition because of “interlock error”.

See "Troubleshooting" (page A-2).

• When the interlock is configured through the SL-VH1S, the pink wire on the transmitter must be insu-

lated from the external (keep open-circuit) because it is not needed if it is not used for other functions.

The interlock reset mechanisms (such as switches) must be installed so that the whole haz-
ardous zone can be checked by the responsible personnel and that operations of the inter-
lock reset mechanisms are not possible within the hazardous zone.

Be sure to confirm absolutely that there is nobody in the hazardous zone, before the inter-
lock is released by the interlock reset mechanism. Failure to follow this warning may result
in significant harm to the machine operators including injury or death.

Other than Automatic start / Automatic reset mode

Blue

0V

Pink (interlock mode selection input)

+24V

Blue

Brown

Brown

0V

Yellow (reset input)

+24V

Short-circuit current 2.5 mA

Transmitter

Main

circuit

Receiver

Main

circuit

Transmitter

Main

circuit

Receiver

Main

circuit

Blue

Pink (interlock mode selection input)

+24V

Blue

Brown

Brown

Yellow (reset input)

Short-circuit current 2.5 mA

When using a PNP output type cable

When using an NPN output type cable

NOTE

Danger