Conditions for termination of override

The override condition is termination if one of the following condition is met.
• All of muting inputs turns OFF state
• Either override input or reset input, or both, turns OFF state.

• Wait input turns ON state.
• SL-V goes to the lockout condition.
• Maximum override period of approx. 60 seconds* has been passed.

* This can be changed through the SL-VH1S.

Time chart

* This can be changed through the SL-VH1S.

The "Maximum override period" can be changed through the SL-VH1S.

Refer to the "SL-VH1S User’s Manual" for information about this configuration.

Within

0.04 to 1 s

100 ms max.

Within approx. 60 s

No limit

No limit

Muting input 1

Muting input 2

Override input

Reset input

Muting lamp

SL-V

OSSD

ON

OFF

ON

OFF

No interruption

Interruption

ON

OFF

ON

OFF

Override condition

No override condition

Light ON

Light OFF

ON

OFF

100 ms max

Override Function Settings

Item

option

Maximum override period

30 second, 1 minute (default), 5 minutes, 15 minutes