Conditions for termination of override
The override condition is termination if one of the following condition is met.
• All of muting inputs turns OFF state
• Either override input or reset input, or both, turns OFF state.
• Wait input turns ON state.
• SL-V goes to the lockout condition.
• Maximum override period of approx. 60 seconds* has been passed.
* This can be changed through the SL-VH1S.
Time chart
* This can be changed through the SL-VH1S.
The "Maximum override period" can be changed through the SL-VH1S.
Refer to the "SL-VH1S User’s Manual" for information about this configuration.
Within
0.04 to 1 s
100 ms max.
Within approx. 60 s
No limit
No limit
Muting input 1
Muting input 2
Override input
Reset input
Muting lamp
SL-V
OSSD
ON
OFF
ON
OFF
No interruption
Interruption
ON
OFF
ON
OFF
Override condition
No override condition
Light ON
Light OFF
ON
OFF
100 ms max
Override Function Settings
Item
option
Maximum override period
30 second, 1 minute (default), 5 minutes, 15 minutes
Cable
Self-diagnosis
Series Connection
Interlock
AUX
EDM
Wait
State Information
Alert
Clear/Blocked
Suspension
Fixed
Reduced
Monitoring