Conditions for initiation of muting, Conditions for termination of muting, Time chart – KEYENCE SL-V Series User Manual
Page 55
2-11
Temporary Suspension of Safety Function
2-31
2
SL-V-M-NO2-E
Conditions for initiation of muting
Muted condition is initiated if all of the following conditions are met.
• Muting input 2 turns ON within 0.04 to 3 seconds after muting input 1 turns ON
• SL-V detects no interruption in the detection zone
• OSSD is ON state and keeps staying for 0.5 seconds or more.
Conditions for termination of muting
Muted condition is terminated if one of the following conditions is met.
• Either of muting inputs goes to OFF state at least for more than 0.02 sec.
• Light curtain goes to lockout condition
• Wait input goes to ON state
• The power supply is interrupted or restored.
• Maximum muting period of approx. 5 minutes has been passed.
Time chart
T1: 0.04 to 3s
• If muting input 2 turns on outside the T1 range after muting input 1 turns on, the SL-V will not mute and
remains in normal operation. (The SL-V does not go into a lockout condition or interlock condition.)
• If only muting input 1 or muting input 2 turn OFF and back ON, the SL-V will not return to the muted
condition. To return to the muted condition, both muting inputs 1 and 2 must first turn OFF and the mut-
ing conditions must be met again.
• If the SL-V power is turned ON while either muting input 1 or 2 is on, the SL-V will not go to a muted
condition. In this case, both muting inputs must be turned OFF and the muting conditions must be met
again.
Muting input 1
Muting input 2
Muting lamp
SL-V
OSSD
ON
OFF
ON
OFF
Muted condition
Not muted condition
Light ON
Light OFF
No
interruption
Interruption
ON
OFF
Response time (ON to OFF)
Response time (OFF to ON)
No limit
T1
T1
20 ms max.
20 ms max.
20 ms max.
20 ms max.
Less than 0.02 s
Less than 0.02 s
Within 5 min
Within 5 min
NOTE
Cable
Self-diagnosis
Series Connection
Interlock
AUX
EDM
Wait
State Information
Alert
Clear/Blocked
Suspension
Fixed
Reduced
Monitoring