Conditions for initiation of muting

Muted condition is initiated if all of the following conditions are met.
• Muting input 2 turns ON within 0.04 to 3 seconds after muting input 1 turns ON
• SL-V detects no interruption in the detection zone

• OSSD is ON state and keeps staying for 0.5 seconds or more.

Conditions for termination of muting

Muted condition is terminated if one of the following conditions is met.

• Either of muting inputs goes to OFF state at least for more than 0.02 sec.
• Light curtain goes to lockout condition
• Wait input goes to ON state

• The power supply is interrupted or restored.
• Maximum muting period of approx. 5 minutes has been passed.

Time chart

T1: 0.04 to 3s

• If muting input 2 turns on outside the T1 range after muting input 1 turns on, the SL-V will not mute and

remains in normal operation. (The SL-V does not go into a lockout condition or interlock condition.)

• If only muting input 1 or muting input 2 turn OFF and back ON, the SL-V will not return to the muted

condition. To return to the muted condition, both muting inputs 1 and 2 must first turn OFF and the mut-

ing conditions must be met again.

• If the SL-V power is turned ON while either muting input 1 or 2 is on, the SL-V will not go to a muted

condition. In this case, both muting inputs must be turned OFF and the muting conditions must be met

again.

Muting input 1

Muting input 2

Muting lamp

SL-V

OSSD

ON

OFF

ON

OFF

Muted condition

Not muted condition

Light ON

Light OFF

No

interruption

Interruption

ON

OFF

Response time (ON to OFF)

Response time (OFF to ON)

No limit

T1

T1

20 ms max.

20 ms max.

20 ms max.

20 ms max.

Less than 0.02 s

Less than 0.02 s

Within 5 min

Within 5 min

NOTE

Cable

Self-diagnosis

Series Connection

Interlock

AUX

EDM

Wait

State Information

Alert

Clear/Blocked

Suspension

Fixed

Reduced

Monitoring