Page 71

2–39
Command Word/Bit Descriptions
Publication 1771-6.5.126 – March 1998
PRC
Movement Set-output Values
When the module starts the Pre-decompression Movement, it:
•
uses ramp rates PRC17-20 and PRC25-28 to ramp outputs
•
sets its outputs to the values listed below
Word
Description
PRC09
Output #1 Set-output Value during Movement [19]
PRC10
Output #2 Set-output Value during Movement [19]
PRC11
Output #3 Set-output Value during Movement [19]
PRC12
Output #4 Set-output Value during Movement [19]
PRC13-16
RFU
Output Ramp Rates
The module uses the following ramp rates when moving its outputs
from setpoint to setpoint during the Pre-decompression Movement.
A ramp rate entry of zero gives a step function ramp (ramp disable).
Word
Description
PRC17
Output #1 Acceleration Ramp Rate during Movement [20]
PRC18
Output #2 Acceleration Ramp Rate during Movement [20]
PRC19
Output #3 Acceleration Ramp Rate during Movement [20]
PRC20
Output #4 Acceleration Ramp Rate during Movement [20]
PRC21-24
RFU
PRC25
Output #1 Deceleration Ramp Rate during Movement [20]
PRC26
Output #2 Deceleration Ramp Rate during Movement [20]
PRC27
Output #3 Deceleration Ramp Rate during Movement [20]
PRC28
Output #4 Deceleration Ramp Rate during Movement [20]
PRC29-32
RFU
End of Movement Set-output Values
When the module completes the Pre-decompression Movement and
HPC03-B09 is SET, it:
•
sets status bit SYS22-B07
•
uses ramp rates PRC17-20 and PRC25-28 when changing outputs
•
sets its outputs to the following values
Word
Description
PRC33
Output #1 Set-output Value at End of Movement [19]
PRC34
Output #2 Set-output Value at End of Movement [19]
PRC35
Output #3 Set-output Value at End of Movement [19]
PRC36
Output #4 Set-output Value at End of Movement [19]
PRC37-56
RFU
Movement Pressure Alarm Setpoint
Word
Description
PRC57
Movement High Pressure Alarm Setpoint [01] The module compares real-time ram (screw) pressure against this entry during the
Pre-decompression Movement. The module sets alarm status bit SYS06-B06 when ram (screw) pressure equals or exceeds this
entry during the Pre- decompression Movement. A zero entry inhibits SYS06-B06.
PRC58 - 64
RFU