beautypg.com

Calibration procedure for outputs – Rockwell Automation 1771-QI,D17716.5.126 PLASTIC MOLD.MODULE User Manual

Page 150

background image

7–8

Calibration Instructions

Publication 1771-6.5.126 – March 1998

After calibrating inputs, calibrate outputs as follows:

change jumpers as required (with power ON)

enter command codes in BTW word 2

enter voltage codes in BTW words 3, 4, 5, and 6

read verification codes in BTR words 10, 11, 12, and 13

Important: Do not remove module from the I/O chassis or turn off

power. Loss of power voids the procedure and requires
that you repeat the entire calibration procedure starting
with inputs.

1. With the power remaining ON, connect the output wiring arm.

2. To calibrate the –10 to +10V dc output range, follow these steps:

Step

Enter Command Code (BTW 2):

and Read in BTR:

1

0020H

word 4 = 000F

2

8020H

word 5 = 000F

3. To verify –10 to +10V range, enter command codes 0100H and 8100H.

Then enter voltage codes:

Step

Enter Voltage Code (BTW 3-6):

and Read Verification Code (BTR 10-13):

1

000H (for 0 volts)

000H

2

0400H (for +5 volts)

0800H

3

7FFH (for +10 volts)

FFFH

4. To calibrate the 0 to +10V dc range, first change these jumpers with

power ON: E11, E12, E15, E16 to the 0 to +10V dc position (bottom)

E16

E11

E15

E12

Step

Enter Command Code (BTW 2):

and Read in BTR:

1

0040H

word 4 = 00FF

2

8040H

word 5 = 00FF

5. To verify 0 to +10V range, enter command codes 0400H and 8400H.

Then enter voltage codes:

Step

Enter Voltage Code (BTW 3-6):

and Read Verification Code (BTR 10-13):

1

000H (for 0 volts)

000H

2

0800H (for +5 volts)

0800H

3

FFFH (for +10 volts)

FFFH

Calibration Procedure
for Outputs