Calibration procedure for outputs – Rockwell Automation 1771-QI,D17716.5.126 PLASTIC MOLD.MODULE User Manual
Page 150
7–8
Calibration Instructions
Publication 1771-6.5.126 – March 1998
After calibrating inputs, calibrate outputs as follows:
•
change jumpers as required (with power ON)
•
enter command codes in BTW word 2
•
enter voltage codes in BTW words 3, 4, 5, and 6
•
read verification codes in BTR words 10, 11, 12, and 13
Important: Do not remove module from the I/O chassis or turn off
power. Loss of power voids the procedure and requires
that you repeat the entire calibration procedure starting
with inputs.
1. With the power remaining ON, connect the output wiring arm.
2. To calibrate the –10 to +10V dc output range, follow these steps:
Step
Enter Command Code (BTW 2):
and Read in BTR:
1
0020H
word 4 = 000F
2
8020H
word 5 = 000F
3. To verify –10 to +10V range, enter command codes 0100H and 8100H.
Then enter voltage codes:
Step
Enter Voltage Code (BTW 3-6):
and Read Verification Code (BTR 10-13):
1
000H (for 0 volts)
000H
2
0400H (for +5 volts)
0800H
3
7FFH (for +10 volts)
FFFH
4. To calibrate the 0 to +10V dc range, first change these jumpers with
power ON: E11, E12, E15, E16 to the 0 to +10V dc position (bottom)
E16
E11
E15
E12
Step
Enter Command Code (BTW 2):
and Read in BTR:
1
0040H
word 4 = 00FF
2
8040H
word 5 = 00FF
5. To verify 0 to +10V range, enter command codes 0400H and 8400H.
Then enter voltage codes:
Step
Enter Voltage Code (BTW 3-6):
and Read Verification Code (BTR 10-13):
1
000H (for 0 volts)
000H
2
0800H (for +5 volts)
0800H
3
FFFH (for +10 volts)
FFFH
Calibration Procedure
for Outputs