9.4 Servo Gain Adjustment Functions

9

Adjustments

9-15

(2) Automatic Gain Switching Function

The automatic gain switching function switches the gain setting between the gain setting 1 and 2 according to the
condition:

Whether position reference is specified or not, or
Position error level, or
AND logic of the above two determined conditions

The position reference of the automatic gain switching condition indicates the reference pulses from CN1.
Note that the automatic gain switching function is disabled for the control modes other than position control.
The existing gain switching function by /G-SEL signal is also available. However, it cannot be used with the
gain switching function.
When the automatic gain switching is enabled by setting 1 to 3 of Pn10B.2, the gain switching function by /G-
SEL signal is disabled.
The following flowchart shows the automatic gain switching.

With or without

position reference

Automatic gain

switching enabled?

Gain switching timer

count-up

Gain switching timer

0 clear

Without

With

Position error

Gain switching timer

count-up

Gain switching timer

0 clear

Position error < Pn125

Automatic gain

switching condition

Position

reference and

Position error

Gain switching timer

count-up

Gain switching timer

0 clear

Without position reference

and

Position error < Pn125

With position reference

or

Position error

≥ Pn125

Position reference only

(Pn10B.2 = 1)

Position error only

(Pn10B.2 = 2)

Position reference

and position error

(Pn10.B = 3)

Disabled (Pn10B.2 = 0)

Timer > Pn124

Gain Setting 2

Gain Setting 1

YES

NO

Enabled (Pn10B.2 = 1 to 3)

Position error

≥ Pn125

End