3) operation in monitor mode, B) output signal monitor display – Yaskawa Sigma II Series SGMVH User Manual
Page 180

7.4 Operation in Monitor Mode (Un)
7
Digital Operator/Panel Operator
7-31
(b) Output Signal Monitor Display
The status of output signal allocated to each output terminal is displayed:
When the output is in OFF (open) status, the top segment (LED) is lit.
When the output is in ON (short-circuited) status, the bottom segment is lit.
Refer to 7.3.3 Output Circuit Signal Allocation for the relation between output terminals and signals.
Note: For the detail of output terminals, refer to 7.3.3 Output Circuit Signal Allocation
.
Seven segments in the top and bottom rows of an LED turn ON and OFF in different combinations to indi-
cate various output signals.
These segments ON for L level and OFF for H level.
• When ALM signal operates (alarm at H level.)
(3) Operation in Monitor Mode
The example below shows how to display the contents of monitor number Un000 when the servomotor rotates at
1500 min
-1
.
4 3 2 1
Top: OFF (H level)
Bottom: ON (L level)
Number
7 6 5
Display LED
Number
Output Terminal
Name
Factory Setting
1
CN1-31, -32
ALM
2
CN1-25, -26
/COIN or /V-CMP
3
CN1-27,
-
28
/TGON
4
CN1-29, -30
/S-RDY
5
CN1-37
ALO1
6
CN1-38
ALO2
7
CN1-39
ALO3
EXAMPLE
The top segment of
number 1 is lit.
4 3 2 1
7 6 5
Step
Display after
Operation
Digital
Operator
Panel
Operator
Description
1
Press the DSPL/SET or MODE/SET Key to select the
monitor mode.
2
Press the UP or DOWN Key to select the monitor num-
ber to be displayed. The display shows the example of
the data of Un000.
3
Press the DATA/ENTER Key once, or DATA/SHIFT
Key for more than one second to display the data of
Un000.
4
Press the DATA/ENTER Key once, or DATA/SHIFT
Key for more than one second to return to the display
of monitor number.
DSPL
SET
(DSPL/SET Key)
MODE/SET
(MODE/SET Key)
DATA
ENTER
(DATA/ENTER
Key)
DATA
(DATA/SHIFT Key)
(Press at least 1 s.)
DATA
ENTER
(DATA/ENTER
Key)
DATA
(DATA/SHIFT Key)
(Press at least 1 s.)