6 Wiring

6.4.2 Wiring for Noise Control

6-18

6.4.2 Wiring for Noise Control

(1) Wiring Example

The SERVOPACK uses high-speed switching elements in the main circuit. It may receive “switching noise”
from these high-speed switching elements if the processing of wiring or grounding around the SERVOPACK is
not appropriate. To prevent this, always wire and ground the SERVOPACK correctly.
The SGDH SERVOPACK has a built-in microprocessor (CPU), so protect it from external noise as much as pos-
sible by installing a noise filter in the appropriate place.
The following is an example of wiring for noise control.
When using a noise filter, follow the precautions in (3) Using Noise Filters.

* 1. For ground wires connected to the casing, use a thick wire with a thickness of

at least 3.5 mm (preferably, plain stitch copper wire).

* 2.

: represents twisted-pair wires.

U

W

V

L2/S

L1/R

L3/T

L3C/t

L1C/r

CN2

SGDM/SGDH
SERVOPACK

Servomotor

Operation relay
sequence
Signal generation
circuit (provided by
customer)

1LF

AVR

(Ground)

(Casing)

(Casing)

(Casing)

(Casing)

(Casing)

(Ground plate)

2LF

3.5 mm
min.

2

200 to 230
VAC

Noise filter

∗1

∗1

∗2

2 mm

2

min.

3.5 mm

ޓmin.

2

∗1

2.0 mm

2

min.

3.5 mm
min.

2

PG

(FG)

M

Wires of 3.5 mm
or more

2

Ground: Ground to an independent ground
(at least class-3 grounding (100

Ω max).)

2LF