6.4 Others

6

Wiring

6-19

* 1. For ground wires connected to the casing, use a thick wire with a thickness of

at least 3.5 mm (preferably, plain stitch copper wire).

* 2.

: represents twisted-pair wires.

(2) Correct Grounding

(a) Grounding the Motor Frame

Always connect servomotor frame terminal FG to the SERVOPACK ground terminal

. Also be sure to

ground the ground terminal

.

If the servomotor is grounded via the machine, a switching noise current will flow from the SERVOPACK
power unit through servomotor stray capacitance. The above grounding is required to prevent the adverse
effects of switching noise.

(b) Noise on the Reference Input Line

If the reference input line receives noise, ground the 0 V line (SG) of the reference input line. If the main cir-
cuit wiring for the motor is accommodated in a metal conduit, ground the conduit and its junction box.
For all grounding, ground at one point only.

M

(FG)

U

W

V

L2/S

L1/R

L3/T

CN2

1LF

∗2

2LF

PG

0 V

+

-

24 VDC

DC24P

DC24N

380 to 480 V

SGDH
SERVOPACK

Servomotor

Operation relay
sequence
Signal generation
circuit (provided by
customer)

(Casing)

(Casing)

(Casing)

(Casing)

(Casing)

(Ground plate)

3.5 mm
min.

2

380 to 480
VAC

Noise filter

∗1

∗1

2 mm

2

min.

3.5 mm

min.

∗1

2.0 mm
min.

3.5 mm
min.

2

Wires of 3.5 mm
or more

Ground: Ground to an independent ground
(at least class-3 grounding (100

Ω max).)

AVR

(Ground)