7.2 Operation in Utility Function Mode (Fn†††)

7

Digital Operator/Panel Operator

7-11

7.2.5 Alarm Traceback Data Clear (Fn006)

This function clears the alarm traceback data, which stores the alarms generated in the SERVOPACK.
After having cleared data, “A.--” (No alarm) is set to all the alarm traceback data.

Step

Display after

Operation

Digital Operator Panel Operator

Description

1

Press the DSPL/SET or MODE/SET Key to select the
utility function mode.

2

Press the UP or DOWN Key to select Fn006.

Note: The enabled digit blinks.

3

Press the DATA/ENTER Key once, or DATA/SHIFT
Key for more than one second, and the display will be
as shown on the left.

4

Press the DSPL/SET or MODE/SET Key to clear the
alarm traceback data.
The display shown on the left blinks for about one sec-
ond when the data is cleared.

5

After about one second

The display changes from “donE” to the display
shown on the left.

6

Press the DATA/ENTER Key once, or DATA/SHIFT
Key for more than one second to return to the utility
function mode display Fn006.