beautypg.com

Important – Yaskawa Sigma II Series SGMVH User Manual

Page 169

background image

7 Digital Operator/Panel Operator

7.2.11 Application Module Detection Results Clear (Fn014)

7-20

7.2.11 Application Module Detection Results Clear (Fn014)

The alarm A.E7 (application module detection error) occurs when turning ON the power for the first time when
the SERVOPACK is used without application module after the SERVOPACK has been used with application
module.
Clearing application module detection results is performed as using the SERVOPACK individually without
operating the application module detection.
Restarting again after performing the following operation will clear and reset the alarm A.E7. Then, the opera-
tion of SERVOPACK without application module is enabled.

Because the parameter is set for the SERVOPACK with an application module, change the setting or initial-
ize the parameter value (Fn005 of utility function mode) as required.

IMPORTANT

Step

Display after

Operation

Digital Operator

Panel Operator

Description

1

Press the DSPL/SET or MODE/SET Key to select
the utility function mode.

2

Press the UP or DOWN Key to select the Fn014.

Note: The enabled digit blinks.

3

Press the DATA/ENTER Key once, or DATA/
SHIFT Key for more than one second, and the dis-
play will be as shown on the left.

4

Press the DSPL/SET or MODE/SET Key, and the
display will be as shown on the left to clear the
application module detection.

5

After about one second

The display changes from “donE” to the display
shown on the left.

6

Press the DATA/ENTER Key once, or DATA/
SHIFT Key for more than one second to return to
the utility function mode.

DSPL

SET

(DSPL/SET Key)

MODE/SET

(MODE/SET Key)

DATA

ENTER

(DATA/ENTER

Key)

DATA

(DATA/SHIFT Key)

(Press at least 1 s.)

Blinks

DSPL

SET

(DSPL/SET Key)

MODE/SET

(MODE/SET Key)

DATA

ENTER

(DATA/ENTER

Key)

DATA

(DATA/SHIFT Key)

(Press at least 1 s.)