6.1 Wiring Main Circuit

6

Wiring

6-7

(4) Three-phase 400 V, 37 kW to 90 kW SERVOPACKs

„

Designing a Power ON Sequence

Note the following points when designing the power ON sequence.

• Design the power ON sequence so that main circuit power supply is turned OFF when a servo alarm signal

is output. See the previous circuit figure.

• Hold the power ON button for at least two seconds. The SERVOPACK will output (1Ry is OFF) a servo

alarm signal for two seconds or less when power is turned ON. This is required in order to initialize the
SERVOPACK.

• Select the power supply specifications for the parts in accordance with the input power supply.

L1/R

DC24P

PG

U