1 interface circuits, Sen signal connection – Yaskawa Sigma II Series SGMVH User Manual
Page 210

8.4 Absolute Encoders
8
Operation
8-29
8.4.1 Interface Circuits
The following diagram shows the standard connections for a an absolute encoder mounted to a servomotor. The
connection cables and wiring pin numbers depend on the servomotor. For details, refer to chapter 5 Specifica-
tions and Dimensional Drawings of Cables and Peripheral Devices.
* 1. :
Represents twisted-pair wires.
* 2. For wiring pin numbers, refer to 5 Specifications and Dimensional Drawings of Cables and Peripheral Devices.
• SEN Signal Connection
Applicable line receiver: Texas Instruments’s SN75175 or the equivalent
Terminating resistance R: 220 to 470
Ω
R
BAT (+)
BAT (-)
PG5 V
PG0 V
PS
/PS
BAT(-)
PCO
/PCO
PBO
/PBO
PAO
/PAO
BAT(+)
SEN
SG
R
R
PA
PB
PC
PS
+5 V
7406
0 V
+
-
4
2
21
22
33
34
35
36
19
1
20
CN1
3
4
5
6
2
1
CN2
UP
DOWN
SG
0 V
Host controller
Battery
SERVOPACK
Encoder
Serial interface
circuit
Serial interface
circuit
Line receiver
Edge
detection
Up/down
counter
Clear
Shield (shell)
Connector
shell
R
PSO
/PSO
48
49
PG
∗1
∗1
∗2
Type
Name
Connector
Pin Number
Setting
Meaning
Input
SEN
CN1-4
OFF (low level)
Input when power is turned ON
ON (high level)
Input at absolute data request
• This input signal is required to output absolute data
from the SERVOPACK.
• When the SERVOPACK main circuit power supply
turns OFF, input the SEN signal at a low level.
• Let at least three seconds elapse after turning ON the
power before changing the SEN signal to high level.
• When the SEN signal changes from low level to high
level, the multiturn data and initial incremental
pulses are output.
Until these operations have been completed, the ser-
vomotor cannot be turned ON regardless of the status
of the servo ON signal (/S-ON).
• The panel operator display will also remain “b.b”.
Refer to 8.4.6 Absolute Encoder Reception Sequence.
IMPORTANT
Maintain the high level for at least 1.3 seconds when the SEN
signal is turned OFF and then ON, as shown in the figure on the
right.
4.7 k
SEN
4
CN1
SG
2
+5V
0V
100
Ω
Ω
0V
0.1
μ
Host controller
SERVOPACK
High level:
About 1 mA
7406 or equivalent
We recommend a PNP transistor.
Signal levels
High: 4.0 V min. Low: 0.8 V max.
OFF
ON (high level)
1.3 s min.
OFF
ON
15 ms min.
SEN signal