10. Power Supply

10.1 External Power Supply Requirements

The voltages must correspond to the following definitions:

Assembly

Power Supply

Voltage Range
DC Mean Value

Max. Current
Consumption

Power Consumption

LE

NC

24V - (VDE 0551)

lower limit

20.4V

...

upper limit

LE 415/425: 1.5A

LE 415/425: approx. 36W

PLC

24V - (VDE 0550)

31V

...

1)

1.8A
if half of the
inputs/outputs are
active simultaneously

approx. 6W
if approx. 1/3 of the
inputs/outputs are active
simultaneously

PL 400
PL 410

21A
if half of the
inputs/outputs are
active simultaneously

approx. 25W
if approx. 1/3 of the
inputs/outputs are active
simultaneously

PA 110

approx. 100mA

approx. 2.9W

1)

Voltages up to 36V

...

are permissible with t < 100ms.

10.1.1 NC Power Supply

24V

1.5Vpp

t

U

The NC part of the LE must not be connected to the control
voltage of the machine tool. It requires its own external
power supply generated separately according to the German
standard VDE 0551.
24V DC voltage with a permissible AC component
(ripple voltage) of 1.5Vpp (recommended filtering capacitor
10 000µF/40V - ).

10.1.2 PLC Power Supply

The PLC part (PLC inputs and outputs) of the LE, PL and PA is operated with a control voltage of 24V- of the
machine tool (generated according to VDE 0550).

The installation and connection of the measuring resistors and the analogue inputs (PL 410, PA 110) must be
safe from contact according to VDE 0160 (section 5.5.1).
If this cannot be ensured, PLC and PL 410 (PA 110) have to be powered according to VDE 0551.
Superimposed AC voltage components arising from a non-controlled three-phase bridge connection with a
ripple factor of 5% (see German standard DIN 40110/10.75, section 1.2) are permissible. Thus the highest
absolute value for the upper voltage limit is 32.6V; the smallest value for the lower voltage limit is 18.5V.

32.6 V
31 V

20.4 V
18.5 V

U

t

The 0V line of the PLC power supply must be connected to
the central signal ground (line

6mm

2

) of the machine tool.

The ground connector on the PL410 housing must be
connected to the protective ground (line

6mm

2

). To avoid

ground loops the measuring voltage at the analogue inputs
must not be grounded.