Function

MP

No.

Bit

A

B

C

Input

AE-6

Entry value

Time constant of armature

1)

X
Y

Z

IV

V
S

2290.0
2290.1
2290.2
2290.3
2290.4
2290.5

-
-
-
-
-
-

-
-
-
-
-
-

Š

Š

Š

Š

Š

Š

0 to 10 000[ms]

Example: Calculation of time constant of the armature from the motor
parameters of the SIEMENS spindle motor 1PH6107-4GN4
SIEMENS motor parameters:

P164 = nom. frequency

= 68.9 Hz

P168 = resistance of armature (cold) = 157 m

P170 = leakage reactance of armat. = 785 m

P171 = reactance of main field

= 12 090 m

MP2290 =

[ ]

[ ]

[ ]

[ ]

(P171 m

P170 m

1000

2

P164 Hz

P168 m

Π

+

[

ms

]

=

=

(12090

785) 1000

2

68,9 157

+

Π

[

ms

]

= 189

[

ms

]

0
0
0
0
0
0

Nominal value of motor

1)

(reference value for "utilization"
display and for I²t monitoring)

X
Y

Z

IV

V
S

2300.0
2300.1
2300.2
2300.3
2300.4
2300.5

-
-
-
-
-
-

-
-
-
-
-
-

Š

Š

Š

Š

Š

Š

0 to 100.000[A]
MP 2300 is used to calculate the l²t monitoring and the utilization
display (modules 9160 and 9166)

0
0
0
0
0
0

Maximum current

1)

of motor

X
Y

Z

IV

V
S

2310.0
2310.1
2310.2
2310.3
2310.4
2310.5

-
-
-
-
-
-

-
-
-
-
-
-

Š

Š

Š

Š

Š

Š

0 to 100.000[A

p

]

The speed controller limits the maximum current to the minimum
value of MP2110 and MP2310.

0
0
0
0
0
0

reserved

2320.x

-

-

Š

entry value 0

0

reserved

2330.x

-

-

Š

entry value 0

0

1)

entry values depending on the motor: see table 2 on page 21.1

R H
1.0 TNC

415B/425/426

Machine Parameters

MP 2290.0 - MP 2330.x

06.03.95

5.2

24