HEIDENHAIN TNC 415 (259 9x0) Service Manual User Manual
Page 202

Function
MP
No.
Bit
A
B
C
Input
AE-6
Entry value
Time constant of armature
1)
X
Y
Z
IV
V
S
2290.0
2290.1
2290.2
2290.3
2290.4
2290.5
-
-
-
-
-
-
-
-
-
-
-
-
0 to 10 000[ms]
Example: Calculation of time constant of the armature from the motor
parameters of the SIEMENS spindle motor 1PH6107-4GN4
SIEMENS motor parameters:
P164 = nom. frequency
= 68.9 Hz
P168 = resistance of armature (cold) = 157 m
Ω
P170 = leakage reactance of armat. = 785 m
Ω
P171 = reactance of main field
= 12 090 m
Ω
MP2290 =
[ ]
[ ]
[ ]
[ ]
(P171 m
P170 m
1000
2
P164 Hz
P168 m
Ω
Ω
Π
Ω
+
⋅
⋅
⋅
⋅
[
ms
]
=
=
(12090
785) 1000
2
68,9 157
+
⋅
⋅
⋅
⋅
Π
[
ms
]
= 189
[
ms
]
0
0
0
0
0
0
Nominal value of motor
1)
(reference value for "utilization"
display and for I²t monitoring)
X
Y
Z
IV
V
S
2300.0
2300.1
2300.2
2300.3
2300.4
2300.5
-
-
-
-
-
-
-
-
-
-
-
-
0 to 100.000[A]
MP 2300 is used to calculate the l²t monitoring and the utilization
display (modules 9160 and 9166)
0
0
0
0
0
0
Maximum current
1)
of motor
X
Y
Z
IV
V
S
2310.0
2310.1
2310.2
2310.3
2310.4
2310.5
-
-
-
-
-
-
-
-
-
-
-
-
0 to 100.000[A
p
]
The speed controller limits the maximum current to the minimum
value of MP2110 and MP2310.
0
0
0
0
0
0
reserved
2320.x
-
-
entry value 0
0
reserved
2330.x
-
-
entry value 0
0
1)
entry values depending on the motor: see table 2 on page 21.1
06.03.95
5.2