MDE-4375 CFN Series Site Controller III Start-Up Manual · June 2005
Page 87
Start-up Commands
5
Type LO TA;C to load the system’s initial quantity, product code and reorder level for each 
tank (tank inventory) (
Figure 12-11: Example of LO TA;C Command with Prompts
6
Type LO F;C to load the pump number, hose number, product code, price code, and tank 
number (
Note: If your site is using MPD’s, you can set them up all at once by typing an asterisk when
prompted for the Pump number. For more details see the Site Manager’s Manual.
The LOad Fuel command automatically sets attribute 8 for that product. If you do not 
want it to be attribute 8, you must disable it. See the Site Manager’s Manual, EN PRO 
command.
Figure 12-12: Example of LO F;C Command with Prompts
7
Type LO CU;C to load the system’s fill limit and slow cutoff for each hose outlet (
Typing just the number is a quantity limit; preceding the number with a dollar sign is a dollar 
limit.
Figure 12-13: Example of LO CU;C Command with Prompts
R* LO TA;C 
Tank number? 1 
Quantity? 9325 
Product code? 1 
Reorder level? 2000 
Tank number? 
R*
R* LO F;C 
Pump number? 2 
Hose number? 1 
Product code? 2 
Price code? 2 
Tank number? 2 
Hose number? 
Pump number? 
R*
R* LO CU;C 
Pump number? 1 
Fill limit? 25 
Slow cutoff? .500 
Pump number? 
R*