beautypg.com

Fuel point setup for ground loop fueling, Fuel point - pump activation test – Gasboy Site Controller III Start-Up User Manual

Page 91

background image

MDE-4375 CFN Series Site Controller III Start-Up Manual · June 2005

Page 79

Pump/Dispenser Automatic Test

Fuel Point Setup for Ground Loop Fueling

This setup must be performed before the system can accept any transactions originating from
the ground loop antenna. This routine only needs to be performed once for each Fuel Point
Reader (FPR), regardless of the number of pumps assigned to the FPR or the number of
vehicles equipped with a Vehicle Module (VM).

1

At the site controller, go to the Individual Parameters menu of the FUELPT.BIN program;
reconfigure one of the ring channels on each FPR to be type "P" (pump).

2

Position a vehicle over the ground loop antenna at one FPR.

3

At the VM, disconnect the T-Ring wires from the GATE connector and move them to the T-
RING connector.

4

Pump some quantity of fuel then hang up the hose.

5

Verify that a transaction was recorded showing the correct VM data.

6

Repeat steps

2

through

5

for each FPR.

7

At the VM, move the T-Ring wires from the GATE connector back to the T-RING connector.

8

At the site controller, go to the Individual Parameters menu of the FUELPT.BIN program;
reconfigure the ring channels for each FPR back to type "L" (ground loop).

Fuel Point - Pump Activation Test

1

Take a hose from the pump and turn on the pump handle.
The pump should not reset. Turn the pump handle off again.

2

Verify that a vehicle has been properly equipped with a programmed Fuel Point Vehicle
Module (VM) and antenna. If equipped with the EID option, touch a valid EID to the EID
Reader and verify that the green lamp on the Reader is lit.

3

If this fueling position is not equipped with a ground loop antenna, skip this step.
Position the vehicle over the ground loop antenna.
The pump should be authorized.
Turn the pump handle on and begin fueling.

4

If this fueling position is equipped with a nozzle antenna ring, turn the pump on and insert the
nozzle into the vehicle.
Within a few seconds, the pump should be activated and fueling can begin.

5

After a few gallons, hang the nozzle back on the pump; verify that the correct EID and VM
data have been recorded.

6

Repeat for all hose outlets.