Communication Tests

Page 70

MDE-4375 CFN Series Site Controller III Start-Up Manual · June 2005

Site Controller III or Remote Terminal

1

Verify that the SC III (and remote terminal, if applicable) is connected properly and that the
monitor is displaying a SC III window or full screen.
If it is not, put the arrow on the SC III icon (by moving the mouse) and double-click on the
icon.

2

Press RETURN.
(You may have to set up switches and parameters on the terminal).
The system should respond: sign on.

3

Type GASBOY and press RETURN.
Note: For security reasons, GASBOY will not display as you type it.

The system should respond: Connected to site 1001 on along with the day, date, and time,
followed by the command prompt (R*).

4

Type P DA and press RETURN.
The system prints the date, time, transaction numbers, sequence number, and version number,
followed by the command prompt (R*).

5

Type LOG MESS...Testing Okidata Printer
The printer should repeat the typed message plus the date and time.

6

Type EX and press RETURN.
The system prints Sign off, along with the day, date, and time. When command terminal and
logger are connected on the same port, the system goes into the monitor mode.