System Power

Page 50

MDE-4375 CFN Series Site Controller III Start-Up Manual · June 2005

Figure 6-1: AC Output Receptacle

Measure

Range

From

To

Hot

Neutral

Measure AC voltage between the H and N screws.
This voltage should be 120 VAC ± 10 percent (108 VAC to 132 VAC).

Hot

Ground

Measure AC voltage between the H and G screws.
This voltage should be 120 VAC ± 10 percent (108 VAC to 132 VAC).

Neutral

Ground

Measure AC voltage between the N and G screws.
This voltage should be 0 VAC ± 1 volt.

Note: If power is not within these specifications, correct it before you continue.