Modem – Gasboy Site Controller III Start-Up User Manual

Page 83

background image

MDE-4375 CFN Series Site Controller III Start-Up Manual · June 2005

Page 71

Communication Tests

Modem

If modem is not supplied by GASBOY, it must be set up using the following parameters:

• modem hangs up with on/off transmission of DTR
• auto answer enabled
• carrier detect present when connection is complete
• jack select RJ41S RJ455
• bell compatible with 103/212A modems
• line error detect disabled
• result code disabled

Note: This procedure verifies remote polling only. This is not a network test. Consult your

network representative for network testing.

1

Turn on the site modem and the modem/data terminal device from which the call will
originate.

2

Set communication program to proper baud rate (9600 default), N, 8, 1
(see the operator's manual that comes with the modem).

3

Dial up the CFN site and establish a communication link with the system.

4

Press RETURN.
The system should respond Sign on.

5

Type GASBOY and press RETURN.
Note: For security reasons, GASBOY will not display as you type it.

The system should respond: Connected to site 1001 on along with the day, date, and time,
followed by the command prompt (R*).

6

Type P DA and press RETURN.
The system prints the date, time, transaction numbers, sequence number, and version number,
followed by the command prompt (R*).

7

Type EX and press RETURN.
The system prints Sign off when connected to the remote port, and terminates the
communication line.

8

Hang up the phone.