Component Power-Up and Configuration
Page 54
MDE-4375 CFN Series Site Controller III Start-Up Manual · June 2005
Standalone Receipt Printer (optional)
Locate the AC power switch on the front of the unit. Push the switch to the right (ON)
position.
Fuel Point Reader (if used)
Locate and turn on the power switch in the top-left side of the FPR. Verify that the power
supply LED, visible through the perforated screen, is lit. Verify that the two RS-485 LEDs,
DL3 and DL4 on the FPR CPU PCB, are flashing.
Configuring the Checkpoint Console
With prior console models, configuration was accomplished with switches and jumpers. This
configuration procedure replaces the switch and jumper settings.
If the console has never been configured or if its configuration has been erased, it will go into
configuration mode at power up. Otherwise, you can access configuration mode by using self-
test 7. Accessing self-test mode is described later in this section. The following table shows
the configuration options and their possible values. The shaded column shows the default
value.
Options
Values
Console poll address
1
2
3
4
Keyswitch type
4 posn
2 posn
Cash drawer
Cash drawer
No cash drawer
Drawer switch type
Dr clo=sw closed
Dr clo=sw open
Beeper
Enabled
Disabled
Alert beep type
15 seconds
8 seconds
4 seconds
2 seconds
Key click type
Short
Medium
Long
No
LED color
Normal
Reverse
Deadman timer
On
Off
Console printer/pad
No cons prnt/pad
Console prnt/pad
Printer address
01
01 - 64
DES
Disabled
Enabled
Receipt line feed, top
00
00 - 10
Receipt line feed, end
10
00 - 18
Receipt left margin
04
00 - 10
Printer
Star SP300
Undefined
Printer port
Serial
Parallel
Decimal position
2 (.00)
3 (.000)
0
1 (.0)
Decimal point type
. (period)
, (comma)
Ignore scan nn
57
31 - 59 62 - 77 99
99
31 - 59 62 - 77 99
99
31 - 59 62 - 77 99
99
31 - 59 62 - 77 99
99
31 - 59 62 - 77 99
Note: If used, console printer address cannot be the same as the ICR receipt printer address.