Jumpers & Switch Settings
Page 40
MDE-4375 CFN Series Site Controller III Start-Up Manual · June 2005
The chart on the right gives the switch settings for the address selections.
8
Pulser Type: Verify that switch SB-5 is set for the proper pulser type, single or dual. Settings
are shown below.
The pulser select switch is set for either single or dual pulsers. If dual pulsers are selected, all
pumps on the pump control unit must have dual pulsers.
Note: The dual pulser type feature requires a PPC Motherboard III and a PPC I/O PCB III.
Both are not yet available; therefore, this switch should be closed.
9
Delay Time: The delay time is the period between activation of the submersible pump and the
activation of the slow flow and fast flow valves. The delay time switches are set to
accommodate a variety of leak detectors used in submersible pump applications. The time
should be set according to the type of leak detector installed on the submersible pump to allow
a normal leak test for each transaction. If different leak detectors are used on each pump, set
the switches to the longest delay time required. Set the delay time to zero seconds for suction
pumps.
Note: The leak detect delay time feature requires a PPC Motherboard III. The PPC
Motherboard III is not yet available; therefore, these switches should be closed.
Address
SB-1
SB-2
SB-3
SB-4
ADDR1
ADDR2
ADDR3
ADDR4
1
Closed
Closed
Closed
Closed
2
Open
Closed
Closed
Closed
3
Closed
Open
Closed
Closed
4
Open
Open
Closed
Closed
5
Closed
Closed
Open
Closed
6
Open
Closed
Open
Closed
7
Closed
Open
Open
Closed
8
Open
Open
Open
Closed
9
Closed
Closed
Closed
Open
10
Open
Closed
Closed
Open
11
Closed
Open
Closed
Open
12
Open
Open
Closed
Open
13
Closed
Closed
Open
Open
14
Open
Closed
Open
Open
15
Closed
Open
Open
Open
16
Open
Open
Open
Open
Pulser Type
SB-5
DUAL
Single
Closed
Dual
Open