beautypg.com

Re-install the expmux pump control cpu board – Gasboy Site Controller III Start-Up User Manual

Page 53

background image

MDE-4375 CFN Series Site Controller III Start-Up Manual · June 2005

Page 41

Jumpers & Switch Settings

10

The settings for switch bank SC (1 through 4) determine when the pump control unit begins
counting pulses for a particular pump. When a switch is open, the PCU begins counting pulses
when the corresponding pump is activated. When a switch is closed, as it should be for most
configurations using mechanical pumps, the PCU does not count pulses for the corresponding
pump until the mechanical reset has completed. The switch should be closed when the pump
is wired for postpay-prepay console operations.

11

In switch bank SC, 5 through 8, only switch 6 and 8 are active. Switch SC-6 is the Deadman
Timer Switch. If enabled, the pump control unit must be polled at least every 15 seconds by
the Site Controller. If it fails to sense a poll at that time, it turns all relays off. If Reset
Complete Mode is used on any pump on a particular PCU, the deadman timer should be
disabled. Switch SC-8 enables the test mode allowing the basic PCU functions to be tested
without the use of a site controller.

12

Re-install the EXPMUX Pump Control CPU board.

Delay Time
(seconds)

SB-6

SB-7

SB-8

RLY1

RLY2

RLY3

0

Closed

Closed

Closed

1

Open

Closed

Closed

2

Closed

Open

Closed

3

Open

Open

Closed

4

Closed

Closed

Open

5

Open

Closed

Open

6

Closed

Open

Open

7

Open

Open

Open

Switch

Function

SC-1

Mode pump 1

Open = Normal, Closed = Reset Complete

SC-2

Mode pump 2

Open = Normal, Closed = Reset Complete

SC-3

Mode pump 3

Open = Normal, Closed = Reset Complete

SC-4

Mode pump 4

Open = Normal, Closed = Reset Complete

Switch

Function

SC-5

No function in on-line mode

SC-6

DEAD

Open - deadman timer enabled

SC-7

No function in on-line mode

SC-8

TEST

Open - Test mode; Closed - On-line mode