Operational settings, N table 25 – Basler Electric BE1-11t User Manual
Page 87
![background image](https://www.manualsdir.com/files/773775/content/doc087.png)
9424200995 Rev H
75
Table 25. Logic Inputs and Outputs
Name
Logic Function
Purpose
Block
Input
Disables the 50BF function when true
50BFI
Input
Starts the 50BF timer when true
52BFI
Input
Starts the 50BF timer when true
Trip
Output
True after the 50BF Delay Timer expires
ReTrip
Output
True when the 50BF Delay Timer is actively timing
Operational Settings
Breaker failure element operational settings are configured on the Breaker Fail (50BF) settings screen
(Figure 53) in BESTCOMSPlus. Settings ranges and defaults are summarized in Table 26.
Figure 53. Breaker Fail Settings Screen
Table 26. Operational Settings
Setting
Range
Increment Unit of Measure
Default
Mode
Disabled or Enabled
n/a
n/a
Disabled
Source
CT Circuit1 or CT Circuit 2
n/a
n/a
CT Circuit 1
Pickup (Phase & Ground)
0 or 0.25 to 10.00 (5A CTs)
0 or 0.05 to 2.00 (1A CTs)
0 or 0.01 to 0.5 (SEF)
varies
amps
0
Control Timer
0 or 50 to 999
varies
milliseconds
50
Delay Timer
0 or 50 to 999
varies
milliseconds
50
BE1-11t
Breaker Failure (50BF) Protection