Operational settings, N table 25 – Basler Electric BE1-11t User Manual

Page 87

background image

9424200995 Rev H

75

Table 25. Logic Inputs and Outputs

Name

Logic Function

Purpose

Block

Input

Disables the 50BF function when true

50BFI

Input

Starts the 50BF timer when true

52BFI

Input

Starts the 50BF timer when true

Trip

Output

True after the 50BF Delay Timer expires

ReTrip

Output

True when the 50BF Delay Timer is actively timing

Operational Settings

Breaker failure element operational settings are configured on the Breaker Fail (50BF) settings screen
(Figure 53) in BESTCOMSPlus. Settings ranges and defaults are summarized in Table 26.

Figure 53. Breaker Fail Settings Screen

Table 26. Operational Settings

Setting

Range

Increment Unit of Measure

Default

Mode

Disabled or Enabled

n/a

n/a

Disabled

Source

CT Circuit1 or CT Circuit 2

n/a

n/a

CT Circuit 1

Pickup (Phase & Ground)

0 or 0.25 to 10.00 (5A CTs)

0 or 0.05 to 2.00 (1A CTs)

0 or 0.01 to 0.5 (SEF)

varies

amps

0

Control Timer

0 or 50 to 999

varies

milliseconds

50

Delay Timer

0 or 50 to 999

varies

milliseconds

50

BE1-11t

Breaker Failure (50BF) Protection