Element Blocking

The Block input provides logic-supervision control of the element. When true, the Block input disables the
element by forcing the Trip and Pickup outputs to logic 0 and resetting the element timer. Connect the
element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.

Logic Connections

Remote analog input element logic connections are made on the BESTlogicPlus screen in
BESTCOMSPlus. The remote analog input element logic block is illustrated in Figure 70. Logic inputs and
outputs are summarized in Table 40.

Figure 70. Remote Analog Input Element Logic Block

Table 40. Logic Inputs and Outputs

Name

Function

Purpose

Block

Input

Disables the analog input element when true

Trip

Output

True when the analog input element is in trip condition

Pickup

Output

True when the analog input element is in pickup condition

Operational Settings

Remote analog input element operational settings are configured on the Remote Analog Input settings
screen (Figure 71) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 41.

Figure 71. Remote Analog Input Settings Screen

Table 41. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled, Over, or Under

n/a

n/a

Disabled

Source

Module 1 or 2, Input 1, 2, 3, or 4

n/a

n/a

Module 1, Input 1

Pickup

–99,999.9 to 99,999.9

0.1

n/a

0

Inhibit

–99,999.9 to 99,999.9

0.1

n/a

0

Time Delay

0 to 60,000

varies

milliseconds

0

Analog Input Protection

BE1-11t