Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.
Logic Connections
Logic timer element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The
logic timer element logic block is illustrated in Figure 81. Logic inputs and outputs are summarized in
Table 44.
Figure 81. Logic Timer Element Logic Block
Table 44. Logic Inputs and Outputs
Name
Logic Function
Purpose
Initiate
Input
Starts the 62 timing sequence
Block
Input
Disables the 62 function when true
Output
Output
True when 62 timing criteria have been met according to mode
Operational Settings
Logic timer element operational settings are configured on the Logic Timers (62) settings screen (Figure
82) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 45.
Figure 82. Logic Timers Settings Screen
Logic Timers (62)