9424200995 Rev H

329

Table 117. Timing Test Settings (3V0 Mode)

Pickup Setting

Time Delay

65 V

2,000 ms

65 V

5,000 ms

65 V

10,000 ms

Step 3: Connect and apply a 75 Vac, single-phase voltage source to terminals C13 (A-phase) and C16

(Neutral).

Step 4: Step the voltage down to 55 volts. Measure the time delay and record the result.

Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 117. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 and 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 for 27X-2, 27X-3, and 27X-4.

Pickup Verification (V1 Mode)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 118 to the BE1-11t. Reset all

targets.

Table 118. Operational Settings (V1 Mode)

Setting

Value

BESTCOMSPlus Screen

Description

Phase VT Ratio

1

System Parameters, Sensing
Transformers

Sets phase VT ratio to 1

Phase VT
Connection

4W-Y

System Parameters, Sensing
Transformers

Sets phase VT connection to
4W-Y

27/59 Mode

PN

System Parameters, Sensing
Transformers

Sets 27/59 mode to phase-
neutral

Element Mode

V1

Protection, Voltage, Undervoltage
(27X-1)

Enables 27X-1 function for V1
mode

Inhibit Level

10 V

Protection, Voltage, Undervoltage
(27X-1)

Sets inhibit level to 10 V

Timing Mode

Definite

Protection, Voltage, Undervoltage
(27X-1)

Selects definite timings

27X-1 V1

Enabled Target Configuration, Targets

Enables V1 target for 27X-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 240.

Blocking is disabled.

OUT1 closes for 27X-1 Trip.

OUT2 closes for 27X-1 Pickup.

Fault recording is enabled.

BE1-11t

Auxiliary Undervoltage (27X) Test