370

9424200995 Rev H

Step 6: Slowly increase the ground current until OUT2 closes and record the pickup. Verify that there is

a 50-1-IND GND target on the front-panel display. Slowly decrease the applied current until
OUT2 opens and record the dropout.

Step 7: Repeat step 6 for the middle and high range pickup settings for your sensing input type. Record

the results.

Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.

Step 9: (Optional.) Repeat steps 1 through 8 for 50-2, 50-3, 50-4, 50-5, 50-6, 50-7, 50-8, and 50-9.

Step 10: (Optional.) Repeat steps 1 through 9 with CT Circuit 2 as the source. In step 5, replace D1 with

F1, D2 with F2, etc.

Timing Verification (IG Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Overcurrent (50-1) screen

and send the first row of test settings in Table 166 to the BE1-11t for settings group 0.

Table 166. Timing Test Settings (IG Mode)

Pickup Setting

Time Delay

0.5 A

2,000 ms

0.5 A

5,000 ms

0.5 A

10,000 ms

Step 2: Prepare to monitor the 50-1 timings. Timing accuracy is verified by measuring the elapsed time

between a sensing current change and OUT1 closing.

Step 3: Connect and apply 0.45 A to BE1-11t terminals D7 and D8 (IG).

Step 4: Step the ground current up to 0.55 A. Measure the time delay and record the result.

Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 166. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 for 50-2, 50-3, 50-4, 50-5, 50-6, 50-7, 50-8, and 50-9.

Step 8: (Optional.) Repeat steps 1 through 7 with CT Circuit 2 as the source. In step 3, replace D1 with

F1, D2 with F2, etc.

Functional Test Report

Pickup Verification (Phase Mode)

Pickup Setting Range = 0.5 to 150 A for 5A sensing

0.1 to 30 A for 1A sensing

Pickup Accuracy =

±2% or ±50 mA, whichever is greater for 5A sensing

±2% or ±10 mA, whichever is greater for 1A sensing

Dropout should occur between 93-99% of the actual pickup value.

Step

Pickup Setting

Low

Actual Pickup

High

Low

*

Actual Dropout

High

*

Pass/Fail

6

0.5 A (5A CT)

0.45 A

0.55 A

0.465 A

0.495 A

P / F

7

5.0 A (5A CT)

4.9 A

5.1 A

4.65 A

4.95 A

P / F

7

20.0 A (5A CT)

20.6 A

20.4 A

18.6 A

19.8 A

P / F

6

0.1 A (1A CT)

0.09 A

0.11 A

0.093 A

0.099 A

P / F

7

1.0 A (1A CT)

0.98 A

1.02 A

0.93 A

0.99 A

P / F

7

4.0 A (1A CT)

3.92 A

4.08 A

3.72 A

3.96 A

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Instantaneous Overcurrent (50) Test

BE1-11t