Basler Electric BE1-11t User Manual
Page 389
9424200995 Rev H
377
Setting
Value
BESTCOMSPlus Screen
Description
Element
Mode
IA
Protection, Current, Instantaneous
Overcurrent (50-1)
Enables 50-1 function
Pickup
2 A
Protection, Current, Instantaneous
Overcurrent (50-1)
Sets pickup to 2 A
Source
CT Circuit 1
Protection, Current, Instantaneous
Overcurrent (50-1)
Selects CT circuit 1 as the
source
Step 8: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 259.
•
50BF Blocking is disabled.
•
50BFI is initiated with 50-1 Trip.
•
52BFI is disabled.
•
OUT1 closes for 50BF Trip.
•
OUT2 closes for 50BF ReTrip.
•
OUT3 closes when minor alarm is true. (Minor Alarm = Breaker Fail)
•
Fault recording is enabled.
•
Breaker Status is disabled.
•
50-1 Blocking is disabled.
Figure 259. BESTlogicPlus Settings (BFI50 Current Supervised BE1-11t Trip Initiate)
Step 9: Verify the BF time delay by applying pickup current (above 2 A) to phase A for at least 100 ms.
A 50BF Trip should occur. Use BESTCOMSPlus to retrieve an SER report and verify that a
50BF Trip was logged 100 milliseconds
±0.5% (1¼ cycles maximum for currents ≥ 5 times the
pickup setting. 1¾ cycles maximum for a current of 2 times pickup. Two cycles maximum for a
current of 1.05 times the pickup setting) after application of pickup current.
Step 10: (Optional.) Raise 50-1 Pickup setting to 10 amps and apply nominal current to the BE1-11t.
Note that OUT1 and OUT2 do not operate. No initiate prevents operation of the breaker failure
function, blocking the breaker fail logic.
Step 11: Verify the Control Time function by using BESTCOMSPlus to send the settings in Table 169 to
the BE1-11t.
BE1-11t
Breaker Fail (50BF) Test