Overvoltage (59) inverse time curve – Basler Electric BE1-11t User Manual
Page 509
9424200995 Rev H
497
Overvoltage (59) Inverse Time Curve
The overvoltage inverse time curve is defined by Equation 34 and shown in Figure 305.
𝑇
𝑇
=
𝐷
�𝑉
𝑚
𝑉
𝑝𝑢
− 1�
Equation 34. Overvoltage (59) Inverse Time Curve Definition
where:
T
T
= Time to Trip
D
= Time Dial
V
m
= Measured Voltage
V
pu
= Voltage Pickup Setting
BE1-11t
Time Curve Characteristics