59p - phase overvoltage protection, 59x - auxiliary overvoltage protection, 60fl - fuse loss – Basler Electric BE1-11t User Manual
Page 476: 62 - logic timers

464
9424200995 Rev H
59P - Phase Overvoltage Protection
Pickup
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................
±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio ................................................ 98%
±1%
Timing Mode
Definite Timing
Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................
±1.5% or ±2 cycles, whichever is greater
Inverse Timing
Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................
±8% or ±4 cycles, whichever is greater
chapter
for information on available timing curves.
59X - Auxiliary Overvoltage Protection
Pickup
Setting Range ........................................................... 1 to 150 V
Accuracy....................................................................
±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio ................................................ 98%
±1%
Timing Mode
Definite Timing
Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................
±1.5% or ±4 cycles, whichever is greater
Inverse Timing
Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................
±8% or ±4 cycles, whichever is greater
chapter
for information on available timing curves.
60FL - Fuse Loss
Time Delay ................................................................ Fixed at 50 ms
62 - Logic Timers
Modes ........................................................................ Pickup/Dropout, One-Shot/Non-Retriggerable,
One-Shot/Retriggerable, Oscillator, Integrating
Timer, Latched
Setting Range ........................................................... 0 to 9,999,000 ms
Accuracy....................................................................
±0.5% or ±12 ms, whichever is greater
67/67N - Directional Current and Polarization Protection
Modes ........................................................................ Forward, Reverse, Non-directional
Maximum Torque Angle ............................................ 0 to 359.9
°
Polarization Methods
●
Zero Sequence Current Polarization (IG)
●
Negative Sequence Polarization (Q)
●
Zero Sequence Polarization (V)
○
VOIN - Calculated Zero Sequence Voltage compared to Calculated Zero Sequence Current.
○
VOIG - Calculated Zero Sequence Voltage compared to Measured Ground Current.
○
VXIN - Measured 3V0-VX Input compared to Calculated Zero Sequence Current.
○
VXIG - Measured 3V0-VX Input compared to Measured Ground Current.
Specifications - 25 Hz Operation
BE1-11t