Inverse time verification, Inverse time reset verification, Definite time verification – Basler Electric BE1-11t User Manual
Page 334

322
9424200995 Rev H
Step
Pickup
Setting
Low
Actual
Pickup
High
Low
*
Actual
Dropout
High
*
Pass/Fail
15
2.36
2.31 V/Hz
2.41 V/Hz
2.289 V/Hz
2.336 V/Hz
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Inverse Time Verification
Time Dial Range = 0.0 to 9.9
Timing Accuracy =
±5% or ±50 ms, whichever is greater
Step
Time
Dial
Setting
Percent of
Nominal V/Hz
Step Voltage
Low
Actual Timing
High
Pass/Fail
3
0.5
110%
132 V
47.5 sec
52.5 sec
P / F
3
0.5
120%
144 V
11.875 sec
13.125 sec
P / F
3
0.5
140%
168 V
2.945 sec
3.255 sec
P / F
4
1.0
110%
132 V
95 sec
105 sec
P / F
4
1.0
120%
144 V
23.75 sec
26.25 sec
P / F
4
1.0
140%
168 V
5.985 sec
6.615 sec
P / F
4
2.0
110%
132 V
190 sec
210 sec
P / F
4
2.0
120%
144 V
47.5 sec
52.5 sec
P / F
4
2.0
140%
168 V
11.875 sec
13.125 sec
P / F
Inverse Time Reset Verification
Time Dial Range = 0.0 to 9.9
Timing Accuracy =
±5% or ±50 ms, whichever is greater
Step
Time Dial Setting
Low
Actual Timing
High
Pass/Fail
3
0.5
5.937 sec
6.562 sec
P / F
4
1.0
11.875 sec
13.125 sec
P / F
4
2.0
23.75 sec
26.25 sec
P / F
Definite Time Verification
Time Dial Range = 0 to 600,000
Timing Accuracy =
±0.5% or ±50 ms, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
3
500 ms
450 ms
550 ms
P / F
4
1,000 ms
950 ms
1,050 ms
P / F
4
5,000 ms
4,950 ms
5,050 ms
P / F
Overexcitation (24) Test
BE1-11t