Timing verification (v1 mode) – Basler Electric BE1-11t User Manual

Page 342

background image

330

9424200995 Rev H

Figure 240. BESTlogicPlus Settings (V1 Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Undervoltage (27X-1) screen and send

the first row of test settings in Table 119 to the BE1-11t.

Table 119. Pickup Test Settings (V1 Mode)

Pickup Setting

Time Delay

78 V

50 ms

38 V

50 ms

22 V

50 ms

Step 4: Prepare to monitor the 27X-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 240).

Step 5: Connect and apply a 240 Vac, single-phase voltage source to terminals C13 (A-phase) and C16

(neutral). For a single-phase input test, V1 = A-phase voltage / 3. Therefore, the BE1-11t should
pick up at a value of three times the setting value when applying only a single-phase input. For
example, to determine the pickup voltage value required for a BE1-11t with a pickup setting of
78, it would require 78 times 3 or 234 volts of input voltage.

Step 6: Slowly decrease the A-phase voltage until OUT2 closes and record the pickup. Verify that there

is a 27X-1-V1 target on the front-panel display. Slowly increase the voltage until OUT2 opens
and record the reset. Reset the target.

Step 7: Verify the pickup and reset accuracy at 120 Vac for a pickup setting of 38 V (114 Vac on test

set) and 70 Vac for a pickup setting of 22 V (66 Vac on test set) as listed in Table 119. Record
the results.

Step 8: (Optional.) Repeat steps 1 through 7 for the B-phase and C-phase voltage inputs.

Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.

Step 10: (Optional.) Repeat steps 1 through 9 for 27X-2, 27X-3, and 27X-4.

Timing Verification (V1 Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Voltage, Undervoltage (27X-1) screen and send

the first row of test settings in Table 120 to the BE1-11t for settings group 0.

Table 120. Timing Test Settings (V1 Mode)

Pickup Setting

Time Delay

38 V

2,000 ms

38 V

5,000 ms

38 V

10,000 ms

Step 2: Prepare to monitor the 27X-1 timings. Timing accuracy is verified by measuring the elapsed

time between a sensing voltage change and OUT1 closing.

Auxiliary Undervoltage (27X) Test

BE1-11t