Basler Electric BE1-11t User Manual
Page 330
318
9424200995 Rev H
Setting
Value
BESTCOMSPlus Screen
Description
Element Mode
Enabled
Protection, Voltage,
Overexcitation
Enables 24 function
24
Enabled
Target Configuration, Targets
Enables target for 24
24 Volts Per Hertz
Major/Non-
Latching
Alarm Configuration, Alarms
Enables alarm for 24
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 237.
•
Blocking is disabled.
•
OUT1 closes for 24 Trip.
•
OUT2 closes for 24 Pickup.
Figure 237. BESTlogicPlus Settings
Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Overexcitation (24) screen and send the
test settings in Table 106 to the BE1-11t.
Table 106. Alarm and Inverse Time Pickup Test Settings
Setting
Value
Description
Inverse Time Pickup
2.1
Sets Inverse Time Pickup at 1.05% of nominal (2.10 V/Hz)
Inverse Time Dial
0
Sets Inverse Time Dial at minimum
Inverse Reset Dial
0
Sets Inverse Reset Dial at minimum
Curve Exponent
2
Sets Curve Exponent to 2
Definite Timer 1 Pickup
0
Disables Definite Timer 1 Pickup
Definite Timer 2 Pickup
0
Disables Definite Timer 2 Pickup
Alarm Pickup
2.05
Sets Alarm at 1.025% of nominal (2.05 V/Hz)
Step 4: Prepare to monitor the operation of the 24 Alarm and Trip functions. Alarm operation can be
verified by monitoring the Major Alarm LED on the protection system's front panel. Operation of
the 24 Trip can be verified by monitoring OUT1.
Step 5: Connect a three-phase, 100 Vac/50-Hz or 120 Vac/60-hertz voltage source (depending on
user's nominal frequency) to Terminals C13 (A-phase), C14 (B-phase), C15 (C-phase), and
C16 (neutral).
Step 6: Apply A-phase voltage at nominal frequency and slowly increase until the Major Alarm LED
lights (V/H PU x Freq x % Alarm = PU) and record the alarm pickup. Slowly decrease the A-
phase voltage until the Major Alarm LED extinguishes and record the dropout.
Step 7: Apply A-phase voltage at nominal frequency and slowly increase until OUT2 closes (V/H Trip x
Freq = PU) and record the pickup. Verify that there is a 24 target on the front-panel display.
Slowly decrease the A-phase voltage until OUT2 opens and record the dropout.
Step 8: (Optional.) Repeat steps 1 through 7 for higher and lower alarm and pickup settings.
Step 9: (Optional.) Repeat steps 1 through 8 for frequencies other than nominal.
Overexcitation (24) Test
BE1-11t