Basler Electric BE1-11t User Manual
Page 291
9424200995 Rev H
279
Figure 227. Basler Electric Device Package Uploader
After rebooting, the Relay Trouble LED on the front panel is lit and Defaults Loaded is displayed on the
Relay Alarms screen. To reset the alarm, use the Metering Explorer in BESTCOMSPlus to navigate to the
Status, Alarms screen (Figure 228) and click the Reset Relay Alarms button. This alarm can also be reset
through the front panel by navigating to Metering > Status > Alarms > Relay Alarms and pressing the
Reset button. Admin access is required to reset the Defaults Loaded alarm. The default username is “A”
and the default password is “A”. Alarm reset can also be set outside of security control, allowing reset
without logging in. Refer to the
chapter for more information. Restore your settings file.
Figure 228. BESTCOMSPlus Alarms Screen
BE1-11t
Device Information