Reactive Power
Reactive power is metered over a range of
−7,500 kilovars to +7,500 kilovars on five ampere nominal
systems. One ampere systems meter reactive power over a range of
−1,500 kilovars to +1,500 kilovars.
Phases A, B, C, and total phase are included.
Apparent Power
Metered apparent power is displayed over a range of –7,500 kilovoltamperes to +7,500 kilovoltamperes
on five-ampere nominal systems. One-ampere nominal systems meter reactive power over a range of
–1,500 kilovoltamperes to +1,500 kilovoltamperes. Phases A, B, C, and total phase are included.
Power Factor
Power factor is metered over a range of maximum lagging (
−0.00) to unity (1.00) to maximum leading
(+0.00) for phases A, B, and C, and for total phase.
Figure 98. Analog Metering, Power Screen
Frequency
Frequency is metered over a range of 10 to 125 hertz. If the measured frequency is outside this range,
the display will show “---“.
Frequency is sensed from Va to N on the back of the BE1-11t. Refer to the
for three-wire and four-wire connection diagrams. The frequency of the auxiliary voltage input (VX) is also
measured.
Frequency metering data is found in BESTCOMSPlus (Figure 99) and on the Metering > Analog Metering
> Frequency screen of the front-panel display.