Retrieving breaker duty information – Basler Electric BE1-11t User Manual
Page 181
![background image](https://www.manualsdir.com/files/773775/content/doc181.png)
9424200995 Rev H
169
Figure 123. Breaker Monitoring Screen
To connect the Block logic input, use the Settings Explorer within BESTCOMSPlus to open the
BESTlogicPlus Programmable Logic tree branch and select the breaker monitor logic block from the list of
Elements. Use the drag and drop method to connect a variable or series of variables to the input. Refer to
the
chapter for more information on setting BESTlogicPlus programmable logic.
The breaker monitor logic block is shown in Figure 124.
Figure 124. Breaker Monitor Logic Block
Table 63 summarizes the Breaker Duty Monitoring settings.
Table 63. Breaker Duty Monitoring Settings
Function
Range/Purpose
Default
Mode
Disabled or Enabled
Disabled
Source
Select CT Circuit 1 or CT Circuit 2
CT Circuit 1
Exponent 1 to 3 in increments of 0.01
0
Max Duty
0 to 42,000,000 in increments of 1
The Max Duty parameter represents the maximum duty that the breaker
contacts can withstand before needing service. Max Duty is programmed in
primary amperes using exponential floating point format.
0.000e+00
Block
Logic input that blocks the breaker monitoring logic when true. When true,
breaker operations are not counted.
0
Retrieving Breaker Duty Information
BESTCOMSPlus Navigation Path: Metering Explorer, Reports, Breaker Monitor
HMI Navigation Path: Metering Explorer, Reports, Breaker Report
Breaker duty values can be read at the front-panel display. Duty values can be changed by using the
front-panel Edit key. Write access to reports is required to edit breaker duty values. Duty values can also
BE1-11t
Breaker Monitoring