Retrieving breaker duty information – Basler Electric BE1-11t User Manual

Page 181

background image

9424200995 Rev H

169

Figure 123. Breaker Monitoring Screen

To connect the Block logic input, use the Settings Explorer within BESTCOMSPlus to open the
BESTlogicPlus Programmable Logic tree branch and select the breaker monitor logic block from the list of
Elements. Use the drag and drop method to connect a variable or series of variables to the input. Refer to
the

BESTlogicPlus

chapter for more information on setting BESTlogicPlus programmable logic.

The breaker monitor logic block is shown in Figure 124.

Figure 124. Breaker Monitor Logic Block

Table 63 summarizes the Breaker Duty Monitoring settings.

Table 63. Breaker Duty Monitoring Settings

Function

Range/Purpose

Default

Mode

Disabled or Enabled

Disabled

Source

Select CT Circuit 1 or CT Circuit 2

CT Circuit 1

Exponent 1 to 3 in increments of 0.01

0

Max Duty

0 to 42,000,000 in increments of 1
The Max Duty parameter represents the maximum duty that the breaker
contacts can withstand before needing service. Max Duty is programmed in
primary amperes using exponential floating point format.

0.000e+00

Block

Logic input that blocks the breaker monitoring logic when true. When true,
breaker operations are not counted.

0

Retrieving Breaker Duty Information

BESTCOMSPlus Navigation Path: Metering Explorer, Reports, Breaker Monitor

HMI Navigation Path: Metering Explorer, Reports, Breaker Report

Breaker duty values can be read at the front-panel display. Duty values can be changed by using the
front-panel Edit key. Write access to reports is required to edit breaker duty values. Duty values can also

BE1-11t

Breaker Monitoring