Read, change, or reset KWH and KVARH records. Use the following to reset the peak current, watt, and
var demand registers to “0” or a pre-existing value:

Breaker Monitoring

BESTCOMSPlus Navigation Path: Metering Explorer, Reports, Breaker Monitor

HMI Navigation Path: Metering Explorer, Reports, Breaker Report

Chapter Reference: Breaker Monitoring

If the Breaker Monitoring features of the BE1-11t are enabled, use the following to reset the counter and
the duty registers to “0” or a pre-existing value:

Relay Trouble Alarms

BESTCOMSPlus Navigation Path: Metering Explorer, Status, Alarms

HMI Navigation Path: Metering Explorer, Status, Alarms

Chapter Reference: Alarms

Reset and verify that the relay trouble alarm is not lit. If required, alarm information can be read by using
the Metering Explorer in BESTCOMSPlus to open the Status, Alarms screen. To attempt clearing a Relay
Trouble Alarm, press the Reset Relay Alarms button or navigate to Metering > Status > Alarms > Relay
Alarms on the front-panel display and press the front-panel Reset button. Refer to the

Alarms

chapter for

setting details.

Major/Minor Programmable Alarms

BESTCOMSPlus Navigation Path: Metering Explorer, Status, Alarms

HMI Navigation Path: Metering Explorer, Status, Alarms

Chapter Reference: Alarms

Reset and verify that the programmable alarms, Major and Minor, as set to meet user needs, are not lit or
asserted. If required, alarm information can be read by using the Metering Explorer in BESTCOMSPlus to
open the Status, Alarms screen. To reset a Major/Minor alarm, press the Reset Major, Minor Alarms
button or navigate to Metering > Status > Alarms > Major or Minor Alarms on the front-panel display and
press the front-panel Reset button. Refer to the

Alarms

chapter for settings details.

Targets

BESTCOMSPlus Navigation Path: Metering Explorer, Status, Targets

HMI Navigation Path: Metering Explorer, Status, Targets

Chapter Reference: Fault Reporting

Reset any active targets and verify that they clear. Targets are reset by navigating to Metering > Status >
Targets on the front-panel display and pressing the Reset button or by using the Metering Explorer in
BESTCOMSPlus to open the Status, Targets screen and clicking on the Reset Targets button. Write
access is required to reset targets through BESTCOMSPlus. Refer to the

Fault Reporting

chapter for

setting details.

Fault Summary Reports

BESTCOMSPlus Navigation Path: Metering Explorer, Reports, Fault Records

HMI Navigation Path: Metering Explorer, Reports, Fault Reports

Chapter Reference: Fault Reporting

Reset “new” fault summary directory records to “0” by using the Metering Explorer in BESTCOMSPlus to
open the Reports, Fault Records screen and clicking on the Reset button. Write access is required. Verify

Commissioning Testing