Phase undervoltage element operational settings are configured on the Undervoltage (27P) settings
screen (Figure 39) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 11.

Figure 39. Phase Undervoltage Settings Screen

Table 11. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled,

One of Three,
Two of Three,

or Three of Three

n/a

n/a

Disabled

Pickup

0 or 1 to 300

0.1

volts

0

Inhibit Level

0 or 1 to 300

0.1

volts

0

Timing Mode

Definite or Inverse

n/a

n/a

Definite

Time Delay (Definite Timing)

50 to 600,000

varies

milliseconds

50

Time Dial (Inverse Timing)

0 to 9.9

0.1

units

0

BE1-11t

Phase Undervoltage (27P) Protection