87n - neutral current differential protection, Automatic setting group characteristics, Bestlogic™plus – Basler Electric BE1-11t User Manual
Page 478

466
9424200995 Rev H
Restraint Slope 1
Setting Range ........................................................... 5 to 100%
Restraint Slope 2
Setting Range ........................................................... 15 to 140%
Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy....................................................................
±1% or ±1 cycle, whichever is greater, plus trip time
for instantaneous response (0.0 setting)
*
* Trip Time for 0.0 Delay Setting .............................. 1¼ cycles maximum for currents ≥ 5 times the pickup
setting. 1¾ cycles maximum for a current of 2
times pickup. Two cycles maximum for a current
of 1.05 times the pickup setting.
87N - Neutral Current Differential Protection
Iop Minimum Pickup
5 Ampere CT
Setting Range ........................................................... 0.1 to 5 A
Accuracy....................................................................
±5% or ±75 mA, whichever is greater
1 Ampere CT
Setting Range ........................................................... 0.02 to 1 A
Accuracy....................................................................
±3% or ±15 mA, whichever
Overcorrection Coefficient
Setting Range ........................................................... 1 to 1.3
Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy....................................................................
±1% or ±1 cycle, whichever is greater, plus trip time
for instantaneous response (0.0 setting)
*
* Trip Time for 0.0 Delay Setting .............................. 1¼ cycles maximum for currents ≥ 5 times the pickup
setting. 1¾ cycles maximum for a current of 2
times pickup. Two cycles maximum for a current
of 1.05 times the pickup setting.
Automatic Setting Group Characteristics
Number of Setting Groups ........................................ 4
Control Modes
Automatic .................................................................. Cold-Load Pickup, Dynamic Load or Unbalance
External ..................................................................... Discrete Input Logic, Binary Input Logic
Switch Threshold
Range ........................................................................ 0.1 to 25 A (5 A), 0.02 to 5 A (1 A)
Accuracy....................................................................
±2% or ±0.05 A (5 A), ±2% or ±0.01 A (1 A)
Switch Time
Range ........................................................................ 0 to 60 min with 1 min increments where
0 = disabled
Accuracy....................................................................
±0.5% or ±2 s, whichever is greater
BESTlogic
™Plus
Update Rate .............................................................. ¼ cycle
Specifications - 25 Hz Operation
BE1-11t