Figure 69. Resistance Temperature Detector Settings Screen

Table 39. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled, Over, Under,

or Over & Under

n/a

n/a

Disabled

Source

RTD Group 1 to RTD Group 7

n/a

n/a

RTD Group 1

Over Pickup

32 to 482 degrees F

or 0 to 250 degrees C

Calculated (F)

1 (C)

degrees

32

Under Pickup

32 to 482 degrees F

or 0 to 250 degrees C

Calculated (F)

1 (C)

degrees

32

Time Delay

0 to 600,000

varies

milliseconds

0

Voting

1 to 24

1

units

1

Remote RTD Metering

RTD metering values are obtained through BESTCOMSPlus by using the Metering Explorer to open the
Analog Metering, RTD Meter tree branch. BESTCOMSPlus must be online with the BE1-11t to view RTD
metering. Alternately, values can be obtained through the front-panel display by navigating to the
Metering, Analog Metering, RTD Meter Input screen.

BE1-11t

Resistance Temperature Detector (49RTD) Protection