Basler Electric BE1-11t User Manual
Page 77

9424200995 Rev H
65
Setting
Range
Increment
Unit of
Measure
Default
Time Delay
0 to 600,000
varies
milliseconds
0
Voltage Inhibit
0 or 15 to 250
0.1
volts
*
20
81ROC
Over Frequency Inhibit
15 to 70 Hz
0.01
hertz
61
Under Frequency Inhibit
15 to 70 Hz
0.01
hertz
59
Negative Sequence
Inhibit
0 to 99
1
percent
20
* Phase-to-phase and phase-to-neutral settings depend on the Phase VT and Aux VT connection
settings. Refer to the
chapter for more information on these settings.
BE1-11t
Frequency (81) Protection