Timing verification (i2 mode, 5a sensing), Timing verification (i2 mode, 1a sensing) – Basler Electric BE1-11t User Manual
Page 403
![background image](https://www.manualsdir.com/files/773775/content/doc403.png)
9424200995 Rev H
391
Dropout should occur between 93-99% of the actual pickup value.
Step
Pickup Setting
Low
Actual
Pickup
High
Low
*
Actual
Dropout
High
*
Pass/Fail
I2
IA
I2
IA
I2
IA
I2
IA
I2
IA
6
0.5
(5A CT)
1.50
0.42
1.26
0.57
1.71
0.46
1.38
0.49
1.47
P / F
7
5.0
(5A CT)
15.00
4.85
14.55
5.15
15.45
4.65
13.95
4.95
14.85
P / F
7
9.0
(5A CT)
27.00
8.73
26.19
9.27
27.81
8.37
25.11
8.91
26.73
P / F
6
0.1
(1A CT)
0.30
0.08
0.24
0.11
0.33
0.093
0.279
0.099
0.297
P / F
7
1.0
(1A CT)
3.00
0.97
2.91
1.03
3.09
0.93
2.79
0.99
2.97
P / F
7
1.8
(1A CT)
5.40
1.74
5.22
1.85
5.55
1.67
5.01
1.78
5.34
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (I2 Mode, 5A Sensing)
Time Dial Range = 0.0 to 9.9
Timing Accuracy =
±5% or ±1½ cycles, whichever is greater
Step
Time Dial
Time Curve
Applied Current
Low
Actual Timing
High
Pass/Fail
4
0.5
I2
3.00 A
0.444 sec
0.491 sec
P / F
4
0.5
I2
7.50 A
0.190 sec
0.240 sec
P / F
4
0.5
I2
27.00 A
0.094 sec
0.174 sec
P / F
4
5.0
I2
3.00 A
4.204 sec
4.647 sec
P / F
4
5.0
I2
7.50 A
1.798 sec
1.988 sec
P / F
4
5.0
I2
27.00 A
1.035 sec
1.145 sec
P / F
4
9.9
I2
3.00 A
8.300 sec
9.173 sec
P / F
4
9.9
I2
7.50 A
3.535 sec
3.907 sec
P / F
4
9.9
I2
27.00 A
2.023 sec
2.237 sec
P / F
Timing Verification (I2 Mode, 1A Sensing)
Time Dial Range = 0.0 to 9.9
Timing Accuracy =
±5% or ±1½ cycles, whichever is greater
Step
Time Dial
Time Curve
Applied Current
Low
Actual Timing
High
Pass/Fail
4
0.5
I2
0.60 A
0.444 sec
0.491 sec
P / F
4
0.5
I2
1.50 A
0.190 sec
0.240 sec
P / F
4
0.5
I2
7.50 A
0.100 sec
0.150 sec
P / F
4
5.0
I2
0.60 A
4.204 sec
4.647 sec
P / F
4
5.0
I2
1.50 A
1.798 sec
1.988 sec
P / F
4
5.0
I2
7.50 A
0.944 sec
1.044 sec
P / F
4
9.9
I2
0.60 A
8.300 sec
9.173 sec
P / F
4
9.9
I2
1.50 A
3.535 sec
3.907 sec
P / F
4
9.9
I2
7.50 A
1.844 sec
2.038 sec
P / F
BE1-11t
Inverse Overcurrent (51) Test