Block initiate 62-x – Basler Electric BE1-11t User Manual
Page 128

116
9424200995 Rev H
Figure 76. One-Shot/Non-Retriggerable Mode
One-Shot/Retriggerable Mode
The one-shot retriggerable timer starts its timing sequence when the Initiate input changes from false to
true. See Figure 77. The timer will time for Delay Time (T1) and then the output will toggle to true for
Duration Time (T2). Additional initiate input changes of state are ignored until the timing sequence has
been completed. If a new false-to-true transition occurs on the Initiate input, the output is forced to logic
false and the timing sequence is restarted. If the T2 timer is set to 0, this timer will not function. The timer
will return to false if the Block input becomes true.
Figure 77. One-Shot/Retriggerable Mode
Oscillator Mode
In this mode, the Initiate input is ignored. See Figure 78. If the Block input is false, the output oscillates
with an ON time (T1) and an OFF time (T2). When the Block input is held true, the oscillator stops and the
output is held off.
Figure 78. Oscillator Mode
Integrating Timer Mode
An integrating timer is similar to a pickup/dropout timer except that the Pickup Time (T1) defines the rate
that the timer integrates toward timing out and setting the output to true. Conversely, the Reset Time (T2)
defines the rate that the timer integrates toward dropout and resetting the output to false. T1 defines the
time delay for the output to change to true if the initiate input becomes true and stays true. T2 defines the
P
0
0
3
5
-3
1
0
2
-2
7
-0
6
Block
Initiate
62-x
P
0
0
3
5
-3
2
0
2
-2
7
-0
6
Block
Initiate
62-x
P
0
0
3
5
-3
3
0
2
-2
7
-0
6
Block
Initiate
62-x
Logic Timers (62)