50 - instantaneous overcurrent protection, 50bf - breaker failure protection – Basler Electric BE1-11t User Manual
Page 474

462
9424200995 Rev H
Time Delay
Setting Range ........................................................... 0 to 600,000 ms
Accuracy....................................................................
±1 s
50 - Instantaneous Overcurrent Protection
Pickup
5 Ampere CT Setting Range ..................................... 0.5 to 150 A
1 Ampere CT Setting Range ..................................... 0.1 to 30 A
SEF Setting Range ................................................... 0.01 to 7.5 A
Unbalanced Setting Range ....................................... 2 to 100%
Dropout ..................................................................... 93 to 99% of the actual pickup value
3Phase, IA, IB, IC, IG Accuracy
5 Ampere CT .............................................................
±4% or ±50 mA, whichever is greater
1 Ampere CT .............................................................
±4% or ±10 mA, whichever is greater
SEF (Pickup Setting of 0.01 to 4.99 A) .....................
±(5% + 4.5 mA)
SEF (Pickup Setting of 5 to 7.5 A) ............................
±(10% + 4.5 mA)
3I0, I1, I2 Accuracy
5 Ampere CT .............................................................
±3% or ±75 mA, whichever is greater
1 Ampere CT .............................................................
±3% or ±15 mA, whichever is greater
Unbalanced Accuracy
5 Ampere CT .............................................................
±3% of pickup setting
1 Ampere CT .............................................................
±3% of pickup setting
Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy
Phase & Ground ........................................................
±1% or ±3 cycles, whichever is greater, plus trip time
for instantaneous response (0.0 setting)
*
Residual ....................................................................
±2% or ±3 cycles, whichever is greater, plus trip time
for instantaneous response (0.0 setting)
*
* Trip Time for 0.0 Delay Setting .............................. 1¼ cycles maximum for currents ≥ 5 times the pickup
setting. 1¾ cycles maximum for a current of 2
times pickup. Two cycles maximum for a current
of 1.05 times the pickup setting.
50BF - Breaker Failure Protection
Phase & Ground Pickup
5 Ampere CT Setting Range ..................................... 0.25 to 10 A
1 Ampere CT Setting Range ..................................... 0.05 to 2 A
SEF ........................................................................... 0.01 to 0.5 A
Accuracy
5 Ampere CT .............................................................
±4% or ±50 mA, whichever is greater
1 Ampere CT .............................................................
±4% or ±10 mA, whichever is greater
SEF ...........................................................................
±(5% + 2.5 mA)
Time Delay & Control Time
Setting Range ........................................................... 50 to 999 ms
Accuracy....................................................................
±1% or +3, –0.5 cycles, whichever is greater
Specifications - 25 Hz Operation
BE1-11t