Operational settings, Table 23 – Basler Electric BE1-11t User Manual
Page 83
9424200995 Rev H
71
Table 23. Logic Inputs and Outputs
Name
Logic Function
Purpose
Block
Input
Disables the 50 function when true
Trip
Output
True when the 50 element is in trip condition
Pickup
Output
True when the 50 element is in pickup condition
Operational Settings
Instantaneous overcurrent element operational settings are configured on the Instantaneous Overcurrent
(50) settings screen (Figure 51) in BESTCOMSPlus. Setting ranges and defaults are summarized in
Table 24.
Figure 51. Instantaneous Overcurrent Settings Screen
Table 24. Operational Settings
Setting
Range
Increment Unit of Measure
Default
Mode
Disabled, IA, IB, IC, 3 Phase,
3I0, I1, I2, IG, or Unbalance
n/a
n/a
Disabled
Source
CT Circuit 1 or CT Circuit 2
n/a
n/a
CT Circuit 1
Pickup
0 or 0.5 to 150 (5A CTs)
0 or 0.1 to 30 (1A CTs)
0 or 0.01 to 7.5 (SEF)
varies
amps
0
2 to 100 (Unbalance mode)
1
percent
Time Delay
0 to 60,000
varies
milliseconds
0
Direction
Forward, Reverse, or Non-Directional
n/a
n/a
Non-Directional
BE1-11t
Instantaneous Overcurrent (50) Protection