Timing verification (vx third harmonic mode), Functional test report, Pickup verification (3v0 mode) – Basler Electric BE1-11t User Manual
Page 363
9424200995 Rev H
351
Step 5: Connect and apply a single-phase, 120 Vac, 3
rd
harmonic voltage source to the Vx input,
terminals C17 (polarity) and C18 (non-polarity).
Step 6: Slowly increase the voltage until OUT2 closes and record the pickup. Verify that there is a 59X-
1-3RD target on the front-panel display. Slowly decrease the voltage until OUT2 opens and
record the dropout. Reset the target.
Step 7: Verify the pickup and dropout accuracy at 70 Vac for a pickup setting of 75 V and 25 Vac for a
pickup setting of 30 V as listed in Table 146. Record the results.
Step 8: (Optional.) Repeat steps 1 through 7 for the B-phase and C-phase voltage inputs.
Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.
Step 10: (Optional.) Repeat steps 1 through 9 for 59X-2, 59X-3, and 59X-4.
Timing Verification (Vx Third Harmonic Mode)
Step 1: Use BESTCOMSPlus to open the Protection, Voltage, Overvoltage (59X-1) screen and send
the first row of test settings in Table 147 to the BE1-11t for settings group 0.
Table 147. Timing Test Settings (Vx Third Harmonic Mode)
Pickup Setting
Time Delay
125 V
2,000 ms
125 V
5,000 ms
125 V
10,000 ms
Step 2: Prepare to monitor the 59X-1 timings. Timing accuracy is verified by measuring the elapsed
time between a sensing voltage change and OUT1 closing.
Step 3: Connect and apply a 120 Vac, single-phase, 3
rd
harmonic voltage source to terminals C17
(polarity) and C18 (non-polarity).
Step 4: Step the voltage up to 130 volts. Measure the time delay and record the result.
Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 147. Record the
results.
Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.
Step 7: (Optional.) Repeat steps 1 through 6 for 59X-2, 59X-3, and 59X-4.
Functional Test Report
Pickup Verification (3V0 Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy =
±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio = 98%
±1%
Step
Pickup
Setting
Low
Actual
Pickup
High
Low
*
Actual
Dropout
High
*
Pass/Fail
3V0
VA
3V0
VA†
3V0
VA†
3V0
VA†
3V0
VA†
6
115.0 265.0 112.7 262.7
117.3 267.3 111.6 261.6
113.9 263.9
P / F
7
65.0
215.0
63.7
213.7
66.3
216.3
63.1
213.1
64.4
214.4
P / F
7
20.0
170.0
19.0
169.0
21.0
171.0
19.4
169.4
19.8
169.8
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
† VA Low and High values are calculated as VA=3V0+150 V nominal.
BE1-11t
Auxiliary Overvoltage (59X) Test