Operational settings – Basler Electric BE1-11t User Manual

Page 114

background image

102

9424200995 Rev H

Operational Settings

Neutral current differential element operational settings are configured on the Neutral Current Differential
(87N) settings screen (Figure 67) in BESTCOMSPlus. Setting ranges and defaults are summarized in
Table 37.

Figure 67. Neutral Current Differential Settings Screen

Table 37. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled or Enabled

n/a

n/a

Disabled

Iop Minimum

0 or 0.1 to 5 (5A CTs)

0 or 0.02 to 1 (1A CTs)

0.01

amps

0

Time Delay

0 to 60,000

varies

milliseconds

0

Overcorrection Coefficient

1 to 1.3

0.01

units

1.10

CT Flip

Yes or No

n/a

n/a

Yes

CT Source

CT1, IG1 or CT2, IG2

n/a

n/a

CT1, IG1

Transient Delay Time

0 to 10,000

varies

milliseconds

0

Neutral Current Differential (87N) Protection

BE1-11t